INSTRUCTION MANUAL
RTD INPUT LIMIT ALARM
model
MP1400 through MP1423
Thank you for choosing M-System. Before use, check specifications
on the unit label.
If you have any problems or questions with the product, please contact
M-System’s Sales Office or representatives.
General Description
The M-PAC Model MP1400 through MP1423 accept 2- or 3-wire RTD
inputs and provide relay contact closure(s) at a preset input level. The
MP1400 Series reflects three styles of output selection:
MP1400 – MP1403 Single (Hi) trip, non-latching (DPDT, 3A)
MP1410 – MP1413 Single (Hi) trip, latching (DPDT, 3A)
MP1420 – MP1423 Dual (Hi/Lo) trip, non-latching (SPDT, 3A)
•Upscale burnout protection as standard
•Failsafe operation available
www.Dat••aDInSedaihcdaebtaoenrtdL4EaUDdj.upcsrootavmbidleedfrom 1 to 100%
Installation [Scale: mm(inch)]
•Operating temperature: -5 to +60°C (23 to 140°F)
•Operating humidity: 30 to 90% RH (non-condensing)
Keep away from water, corrosive gas, dust and vibration. DIN rail
mounting available for 11-pin-base modules. Use DIN rail of 35 mm
width.
•11-Pin Base
55 (2.17) min.
40 ± 0.2
40 ± 0.2 2–M4 SCREW
(1.57± .01) (1.57± .01)
Adjustments
•Setpoint The MP1400 Series has five styles of setpoint adjustment:
MP14X0 Top-accessed, 3-turn screw(s)
MP14X2 Remote dial connection(s), 1k to 100k ohms
MP14X3 DC-programmable, 0 to 1V
The setpoint is adjustable over the entire input span.
A) Set deadband at its minimum (fully counterclockwise) before ad-
justing the setpoint.
B) With the specified trip Resistance/RTD input applied, adjust setpoint
until the relay trips. For Hi trip calibration, start with the setpoint
above the desired trip. For Lo trip calibration start below the desired
trip.
•Deadband The deadband is independently adjustable for both
setpoints in dual alarms.
A) Set deadband at its minimum (fully counterclockwise). Set setpoint
to desired trip.
B) Adjust Resistance/RTD input until relay trips.
C) Re-adjust deadband to 100% (fully clockwise).
D) Set Resistance/RTD input to desired deadband position.
E) Slowly adjust deadband until relay untrips.
•Transmitter Output (Option T)
A) With the specified minimum input applied, adjust Zero for 0.00V at
the transmitter output.
B) With the specified maximum input applied, adjust Span for 1.00V.
Repeat A) to B) for best accuracy.
Relay Protection
•Output Relay Rating 30V DC @3A (resistive load) or
120V AC @3A (cosø=1)
For maximum relay life with inductive loads, external protection is
recommended. Refer to the Figures below.
•20-Pin Base
85 (3.35) min.
56 ± 0.2
(2.20 ±0.01)
56 ± 0.2
(2.20 ±0.01)
2–M4 SCREW
•DC Line Powered Loop Place a diode across the load.
DC Power
Limit Alarm
LOAD
•AC Line Powered Loop Place a varistor or CR spark killer across
the load.
AC Power
Terminal Connections
Make wiring to terminals as shown in the Tables in Page 2 through 3.
Use the socket provided with the module.
Limit Alarm
LOAD
Spark Quenching
Circuit
P. 1 / 3 EM-9804 Rev.3

1 Page





MP1402 pdf, ピン配列
MP1400 through MP1423
•Latching Output
MP1410
MP1410
w/Option T
1 POWER (Hot/+) 1 POWER (Hot/+)
2 No Connection
2 No Connection
3 POWER (Neu/–) 3 POWER (Neu/–)
4 Latch Reset
4 Latch Reset
5 No Connection
5 No Connection
6 No Connection
6 No Connection
7 No Connection
7 No Connection
8 No Connection
8 SP Xmtr +
9 RTD Lo
9 RTD Lo
10 No Connection 10 Xmtr Common
11 RTD Hi
11 RTD Hi
12 No Connection 12 Proc Xmtr +
13 N.O.
13 N.O.
14 COM *
14 COM *
15 N.C. *
15 N.C. *
16 Latch Reset
16 Latch Reset
17 N.O.
17 N.O.
18 COM
18 COM
19 N.C.
19 N.C.
www.Data2S0 hRTeDeCt4omUp .Lceaodm 20 RTD Comp Lead
MP1412
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 Latch Reset
5 SP Pot CCW
6 SP Pot W
7 SP Pot CW
8 No Connection
9 RTD Lo
10 No Connection
11 RTD Hi
12 No Connection
13 N.O.
14 COM *
15 N.C. *
16 Latch Reset
17 N.O.
18 COM
19 N.C.
20 RTD Comp Lead
MP1412
w/Option T
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 Latch Reset
5 SP Pot CCW
6 SP Pot W
7 SP Pot CW
8 SP Xmtr +
9 RTD Lo
10 Xmtr Common
11 RTD Hi
12 Proc Xmtr +
13 N.O.
14 COM *
15 N.C. *
16 Latch Reset
17 N.O.
18 COM
19 N.C.
20 RTD Comp Lead
MP1413
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 Latch Reset
5 SP –
6 SP +
7 No Connection
8 No Connection
9 RTD Lo
10 No Connection
11 RTD Hi
12 No Connection
13 N.O.
14 COM *
15 N.C. *
16 Latch Reset
17 N.O.
18 COM
19 N.C.
20 RTD Comp Lead
MP1413
w/Option T
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 Latch Reset
5 SP –
6 SP +
7 No Connection
8 SP Xmtr +
9 RTD Lo
10 Xmtr Common
11 RTD Hi
12 Proc Xmtr +
13 N.O.
14 COM *
15 N.C. *
16 Latch Reset
17 N.O.
18 COM
19 N.C.
20 RTD Comp Lead
KEYS
N.O. = Normally Open
COM = Common
N.C. = Normally Closed
Proc = Process
Xmtr = Transmitter
SP = Setpoint
W = Wiper
CW = Clockwise
CCW =
␣ ␣ ␣ ␣ ␣ ␣ ␣ ␣ ␣ ␣ Counterclockwise
*Pins used for
Option V
20-pin = 14(+) - 15(–)
•Dual Output
MP1420
1 POWER (Hot/+)
2 RTD Comp Lead
3 POWER (Neu/–)
4 RTD Hi
5 RTD Lo
6 N.O.
7 COM *␣ ␣ ␣ ␣ ␣ ␣ Hi Set
8 N.C. *
9 N.O.
10 COM *␣ ␣ ␣ ␣ ␣ ␣ Lo Set
11 N.C. *
MP1420
w/Option T
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 No Connection
5 No Connection
6 Xmtr Common
7 No Connection
8 No Connection
9 RTD Lo
10 Proc Xmtr +
11 RTD Hi
12 Lo SP Xmtr +
13 N.O.
14 COM *␣ ␣ ␣ ␣ ␣ ␣ Lo Set
15 N.C. *
16 Hi SP Xmtr +
17 N.O.
18 COM *␣ ␣ ␣ ␣ ␣ ␣ Hi Set
19 N.C. *
20 RTD Comp Lead
MP1422
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 Lo SP Pot CW
5 Lo SP Pot W
6 SP Pots CCW
7 Hi SP Pot W
8 Hi SP Pot CW
9 RTD Lo
10 No Connection
11 RTD Hi
12 No Connection
13 N.O.
14 COM *␣ ␣ ␣ ␣ ␣ ␣ Lo Set
15 N.C. *
16 No Connection
17 N.O.
18 COM *␣ ␣ ␣ ␣ ␣ ␣ Hi Set
19 N.C. *
20 RTD Comp Lead
MP1422
w/Option T
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 Lo SP Pot CW
5 Lo SP Pot W
6 SP Pots CCW/
Xmtr Common
7 Hi SP Pot W
8 Hi SP Pot CW
9 RTD Lo
10 Proc Xmtr +
11 RTD Hi
12 Lo SP Xmtr +
13 N.O.
14 COM *␣ ␣ ␣ ␣ ␣ ␣ Lo Set
15 N.C. *
16 Hi SP Xmtr +
17 N.O.
18 COM *␣ ␣ ␣ ␣ ␣ ␣ Hi Set
19 N.C. *
20 RTD Comp Lead
MP1423
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 No Connection
5 Lo SP +
6 SP Common
7 Hi SP +
8 No Connection
9 RTD Lo
10 No Connection
11 RTD Hi
12 No Connection
13 N.O.
14 COM *␣ ␣ ␣ ␣ ␣ ␣ Lo Set
15 N.C. *
16 No Connection
17 N.O.
18 COM *␣ ␣ ␣ ␣ ␣ ␣ Hi Set
19 N.C. *
20 RTD Comp Lead
MP1423
w/Option T
1 POWER (Hot/+)
2 No Connection
3 POWER (Neu/–)
4 No Connection
5 Lo SP +
6 SP Common/
Xmtr Common
7 Hi SP +
8 No Connection
9 RTD Lo
10 Proc Xmtr +
11 RTD Hi
12 Lo SP Xmtr +
13 N.O.
14 COM *␣ ␣ ␣ ␣ ␣ ␣ Lo Set
15 N.C. *
16 Hi SP Xmtr +
17 N.O.
18 COM *␣ ␣ ␣ ␣ ␣ ␣ Hi Set
19 N.C. *
20 RTD Comp Lead
•Terminal No. for 11-Pin Base
87
65
4
•Terminal No. for 20-Pin Base
975431
86
2 20
KEYS
N.O. = Normally Open
COM = Common
N.C. = Normally Closed
Proc = Process
Xmtr = Transmitter
SP = Setpoint
W = Wiper
CW = Clockwise
CCW =
␣ ␣ ␣ ␣ ␣ ␣ ␣ ␣ ␣ ␣ Counterclockwise
*Pins used for
Option V
20-pin:
␣ ␣ Hi Set = 19(+) - 18(–)
␣ ␣ Lo Set = 15(+) - 14(–)
11-pin:
␣ ␣ Hi Set = 7(+) - 8(–)
␣ ␣ Lo Set = 10(+) - 11(–)
9
10 11
3
12
10 12
16 18
11 13 14 15 17 19
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such product
was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies, under this
warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under
this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL
DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
P. 3 / 3 EM-9804 Rev.3


3Pages





ページ 合計 : 3 ページ
 
PDF
ダウンロード
[ MP1402 データシート.PDF ]


データシートを活用すると、その部品の主な機能と仕様を詳しく理解できます。 ピン構成、電気的特性、動作パラメータ、性能を確認してください。


共有リンク

Link :


部品番号部品説明メーカ
MP1400

(MP1400 - MP1423) RTD Input Limit Alarm

M-System
M-System
MP1402

(MP1400 - MP1423) RTD Input Limit Alarm

M-System
M-System
MP1403

(MP1400 - MP1423) RTD Input Limit Alarm

M-System
M-System
MP140x

(MP1400 - MP1423) RTD Input Limit Alarm

M-System
M-System


www.DataSheet.jp    |   2020   |  メール    |   最新    |   Sitemap