ES825-100F/XF/CF Leak Sensors
Installation Instructions
Sensor Model
ES825-100F
ES825-100XF (Extended Temperature)
ES825-100CF (Chemical Resistant)
Non-Discriminating Leak Sensor
w/Supervised Wiring and
Fault Detection, 24 VDC
For use with the
following consoles:
LC2000
TMS3000
TMS2000
NOTE: ES825-100 SERIES SENSORS ARE NOT COMPATIBLE
WITH Wireless DATA ACQUISITION MODULE (WiDAM) USED
IN CONJUNCTION WITH WIRELESS CONSOLES. REFER TO
THE ES825-300 SERIES.
Bulletin 142 Rev. E (04/09/10)
© COPYRIGHT 2010 PNEUMERCATOR CO., INC.
TEL: (631) 293-8450
FAX: (631) 293-8533
WEBSITE: www.pneumercator.com
PNEUMERCATOR TECHNICAL SUPPORT
1 (800) 209-7858
2/22/2013 12:54:35 PM, 1:1, © COPYRIGHT 2013 PNEUMERCATOR COMPANY, INC.
Page 1 of 4

1 Page





ES825-100F pdf, ピン配列
WIRING:
! WARNING
Refer to console installation manual for WARNINGS and CAUTIONS before proceeding. FAILURE TO
COMPLY MAY RESULT IN PERSONAL INJURY, PROPERTY LOSS AND EQUIPMENT DAMAGE.
CONSOLE
INTRINSICALLY SAFE
WIRING COMPARTMENT
1" NPT FITTING (TMS3000)
3/4" NPT FITTING (LC2000, TMS2000)
NON-HAZARDOUS
AREA
HAZARDOUS AREA
CLASS I, GROUPS C,D
SECONDARY
CONTAINMENT
AREA
VAPOR SEAL
(AS REQ'D)
SENSOR
CABLE
JUNCTION BOX
(SEE SENSOR WIRING)
SENSOR
CABLE SELECTION:
Use Belden 8443, or Alpha 1173C or any
equivalent 3-conductor, 22 AWG cable, refer
to console installation manual for more cable
selection and limitation information. Shielded
cable is not required, but if used, the shield
wire must be connected to the SENSOR
GROUND TERMINAL in the console I.S.
compartment and should be cut back and left
unterminated at the sensor junction box.
TYPICAL WIRING FOR SENSOR
WIRE SPLICE SEAL CONNECTOR
FOLLOW SUPPLIED WIRE SPLICE INSTRUCTIONS
BULLETIN 180; KIT P/N 10585-3
WATERTIGHT RATED BOX
SUPPLIED BY INSTALLER
TO SENSOR
SENSOR CABLE
CABLE GRIP
REDUCER FITTING
(IF NEEDED)
Bulletin 142 Rev. E (04/09/10)
2/22/2013 12:54:37 PM, 1:1, © COPYRIGHT 2013 PNEUMERCATOR COMPANY, INC.
CONDUIT AND VAPOR SEAL FITTING
(SIZE AND LOCATION TO BE DETERMINED
BY QUALIFIED INSTALLER)
TO CONSOLE
(AS SHOWN ON NEXT PAGE)
BLK TO BLK
RED TO RED
WHT * TO WHT *
* WHT OR GRN
FIELD CABLE
Note: Shielded cable is not
required, but if used, the shield
wire must be connected to the
SENSOR GROUND TERMINAL
in the console I.S. compartment
and should be cut back and left
unterminated at the sensor
junction box.
Page 3 of 4


3Pages





ページ 合計 : 4 ページ
 
PDF
ダウンロード
[ ES825-100F データシート.PDF ]


データシートを活用すると、その部品の主な機能と仕様を詳しく理解できます。 ピン構成、電気的特性、動作パラメータ、性能を確認してください。


共有リンク

Link :


部品番号部品説明メーカ
ES825-100CF

Leak Sensors

PNEUMERCATOR
PNEUMERCATOR
ES825-100F

Leak Sensors

PNEUMERCATOR
PNEUMERCATOR
ES825-100XF

Leak Sensors

PNEUMERCATOR
PNEUMERCATOR


www.DataSheet.jp    |   2020   |  メール    |   最新    |   Sitemap