Product data sheet
Characteristics
Complementary
Network frequency
[Ue] rated operational voltage
Magnetic tripping limit
Breaking capacity
[Ics] rated service breaking capacity
Limitation class
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
Contact position indicator
Control type
Local signalling
Mounting mode
Mounting support
Nov 4, 2012
A9F74110
miniature circuit breaker - iC60N - 1 pole - 10 A
- C curve
Main
Circuit breaker applica-
tion
Range of product
Device short name
Poles description
Number of protected
poles
[In] rated current
Network type
Trip unit technology
Curve code
Utilisation category
Suitability for isolation
Distribution
IC60
IC60N
1P
1
10 A
AC
DC
Thermal-magnetic
C
Category A EN 60947-2
Category A IEC 60947-2
Yes EN 60898-1
Yes EN 60947-2
Yes IEC 60898-1
Yes IEC 60947-2
50/60 Hz
100...130 V AC 50/60 Hz
12...60 V AC 50/60 Hz
12...72 V DC
220...240 V AC 50/60 Hz
230/400 V AC 50/60 Hz
8 x In +/- 20 %
10 kA Icu EN 60947-2 220...240 V AC 50/60 Hz
10 kA Icu IEC 60947-2 220...240 V AC 50/60 Hz
20 kA Icu EN 60947-2 100...130 V AC 50/60 Hz
20 kA Icu IEC 60947-2 100...130 V AC 50/60 Hz
36 kA Icu EN 60947-2 12...60 V AC 50/60 Hz
36 kA Icu IEC 60947-2 12...60 V AC 50/60 Hz
6 kA Icu EN 60947-2 12...72 V DC
6 kA Icu IEC 60947-2 12...72 V DC
6000 A Icn EN 60898-1 230/400 V AC 50/60 Hz
6000 A Icn IEC 60898-1 230/400 V AC 50/60 Hz
6 kA 100 % EN 60947-2 12...72 V DC
6 kA 100 % IEC 60947-2 12...72 V DC
15 kA 75 % EN 60947-2 100...130 V AC 50/60 Hz
27 kA 75 % EN 60947-2 12...60 V AC 50/60 Hz
7.5 kA 75 % EN 60947-2 220...240 V AC 50/60 Hz
15 kA 75 % IEC 60947-2 100...130 V AC 50/60 Hz
27 kA 75 % IEC 60947-2 12...60 V AC 50/60 Hz
7.5 kA 75 % IEC 60947-2 220...240 V AC 50/60 Hz
3 EN 60898-1
3 IEC 60898-1
500 V AC 50/60 Hz EN 60947-2
500 V AC 50/60 Hz IEC 60947-2
6 kV EN 60947-2
6 kV IEC 60947-2
Yes
Toggle
Trip indicator
Removable comb busbar installed
DIN rail
1

1 page





PáginasTotal 2 Páginas
PDF Descargar[ Datasheet A9F74110.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
A9F74110miniature circuit breakerSchneider
Schneider

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar