DataSheet.jp

G3PA の電気的特性と機能

G3PAのメーカーはOMRONです、この部品の機能は「Extremely Thin Relays Integrated」です。


製品の詳細 ( Datasheet PDF )

部品番号 G3PA
部品説明 Extremely Thin Relays Integrated
メーカ OMRON
ロゴ OMRON ロゴ 




このページの下部にプレビューとG3PAダウンロード(pdfファイル)リンクがあります。

Total 18 pages

No Preview Available !

G3PA Datasheet, G3PA PDF,ピン配置, 機能
Solid State Relays
G3PA
Extremely Thin Relays Integrated with Heat Sinks
• Downsizing achieved through optimum design of heat sink.
• Mounting possible via screws or via DIN track.
• Close mounting possible for linking terminals. (Except for
G3PA-260B-VD and G3PA-450B-VD-2.)
• Applicable with 3-phase loads.
• Replaceable power element cartridges.
• Complies with VDE 0160 (finger protection), with a dielec-
tric strength of 4,000 V between input and load.
• Complies with VDE 0805, IEC 950.
• Certified by UL, CSA, and VDE (reinforced insulation).
Ordering Information
List of Models
To Order: Select the part number and add the rated input voltage range. (e.g., G3PA-430B-VD-2 DC12-24)
Isolation
Phototriac
coupler
Zero cross function
Yes
No
Yes
Indicator
Yes
Rated output load
10 A at 24 to 240 VAC
20 A at 24 to 240 VAC
40 A at 24 to 240 VAC
60 A at 24 to 240 VAC
10 A at 24 to 240 VAC
20 A at 24 to 240 VAC
40 A at 24 to 240 VAC
60 A at 24 to 240 VAC
10 A at 24 to 240 VAC
20 A at 24 to 240 VAC
40 A at 24 to 240 VAC
60 A at 24 to 240 VAC
20 A at 180 to 400 VAC
30 A at 180 to 400 VAC
20 A at 200 to 480 VAC
30 A at 200 to 480 VAC
50 A at 200 to 480 VAC
Rated input voltage
5 to 24 VDC
24 VAC
12 to 24 VDC
Model
G3PA-210B-VD
G3PA-220B-VD
G3PA-240B-VD
G3PA-260B-VD
G3PA-210BL-VD
G3PA-220BL-VD
G3PA-240BL-VD
G3PA-260BL-VD
G3PA-210B-VD
G3PA-220B-VD
G3PA-240B-VD
G3PA-260B-VD
G3PA-420B-VD
G3PA-430B-VD
G3PA-420B-VD-2
G3PA-430B-VD-2
G3PA-450B-VD-2
Solid State Relays G3PA
437
http://www.Datasheet4U.com

1 Page





G3PA pdf, ピン配列
Characteristics
Item
G3PA-
G3PA-
G3PA-
G3PA-
G3PA-
G3PA-
G3PA-
G3PA-
G3PA-
210B(L)-VD 220B(L)-VD 240B(L)-VD 260B(L)-VD 420B-VD 420B-VD-2 430B-VD 430B-VD-2 450B-VD-2
Operate time 1/2 of load power source cycle + 1 ms max. (DC Input, -B models)
1 1/2 of load power source cycle + 1 ms max. (AC Input)
1 ms max. (-BL models)
Release time 1/2 of load power source cycle + 1 ms max. (DC Input)
1 1/2 of load power source cycle + 1 ms max. (AC Input)
Output ON 1.6 V (RMS) max.
voltage drop
1.8 V (RMS) max.
Leakage
current
5 mA max. (at 100 VAC) 10 mA max. (at 100 VAC)
10 mA max. (at 200 VAC) 20 mA max. (at 200 VAC)
20 mA 20 mA max. (at 20 mA 20 mA max. (at 480 VAC)
max. (at 480 VAC)
max. (at
400 VAC)
400 VAC)
I2t 260 A2s
1,260 A2s
260 A2s 1,800 A2s
1,800 A2s
1,800 A2s
Insulation 100 MΩ min. (at 500 VDC)
resistance
Dielectric
strength
4,000 VAC, 50/60 Hz for 1 min
Vibration Malfunction: 10 to 55, 0.75–mm double amplitude (Mounted to DIN track)
resistance
Shock
Malfunction: 300 m/s2 (mounted to DIN track)
resistance
Ambient
Operating:–30°C to 80°C (with no icing or condensation)
temperature Storage:–30°C to 100°C (with no icing or condensation)
Certified
standards
UL, CSA, EN60950 File No. 5915ÜG
UL, CSA , UL, CSA,
EN60947- EN60947-4-3
4-3 File File No.
No. 133127ÜG
6642ÜG
UL, CSA, UL, CSA, EN60947-4-3 File
EN60947- No. 133127ÜG
4-3 File
No.
6642ÜG
Ambient
humidity
Operating: 45% to 85%
Weight
Approx.
260 g
Approx.
340 g
Approx.
460 g
Approx.
900 g
Approx. Approx.
290 g
290 g
Approx. Approx.
410 g
410 g
Approx.
900 g
Solid State Relays G3PA 439


3Pages


G3PA 電子部品, 半導体
3. Insert the cartridge into the opening of the G3P A so tha t side A
and side B are even.
Side A
Side B
4. Tighten the screws on both the corners with a tightening torque of
0.59 to 0.78 Nm.
5. Tighten the screws on both the sides with a tightening torque of
0.59 to 0.78 Nm.
6. Attach the terminal cover.
7. Switch on the power and check the G3PA to be sure it works
properly.
Linking Terminal Connection
Connecting w ith lin king ter minal f or G3 PA-210B(L)-VD, -22 0B(L)-
VD, -240B(L)-VD and G3PA-420B-VD(-2), G3PA-430B-VD(-2).
SSR1
SSR2
SSR1
SSR2
Connecting with lin king ter minal to “G32A-D” ser ies short circuit
unit. (Order short circuit units seperately.)
SSR G32A Unit
SSR G32A Unit
1. When SSRs are close
mounted, loosen the
M3.5 Sems screw and
flip the linking terminal
down.
2. Insert the linking
terminal securely
into the center of
the screw and
tighten the screw.
1. When SSR are close
mounted, loosen the
M3.5 Sems screw on
the G32A and flip the
linking terminal down.
*
* The cover will not fit if
the terminal protrudes.
2. Insert the linking terminal
securely into the center
of the screw and tighten
the screw. Ensure that
the linking terminal does
not protrude.
Connect the terminal with power off.
Linking terminal
Refer to the instruction manual for
the G32A-A Power Device Cartridge
to replace the G3PA's triac part.
Linking terminal
G3PA-420B-VD
Linking
terminal
Linking
terminal
When the temperature indicator has turned from pink to red, the G32-A-A Power Device Cartridge Use the terminal cover to prevent accidents
may have malfunctioned, in which case the cartridge must be replaced with a new one.
due to electric shock.
442 Solid State Relays G3PA

6 Page



ページ 合計 : 18 ページ
 
PDF
ダウンロード
[ G3PA データシート.PDF ]


データシートを活用すると、その部品の主な機能と仕様を詳しく理解できます。 ピン構成、電気的特性、動作パラメータ、性能を確認してください。


共有リンク

Link :


部品番号部品説明メーカ
G3PA

Extremely Thin Relays Integrated

OMRON
OMRON
G3PA-VD

Extremely Thin Relays Integrated

OMRON
OMRON
G3PC

SSR

Omron
Omron
G3PC-220B-VD

SSR

Omron
Omron


www.DataSheet.jp    |   2020   |  メール    |   最新    |   Sitemap