SYSMAC CJ-series CJ2M CPU Units
CJ2M-CPU3@/-CPU1@www.DataSheet4U.com
CSM_CJ2M-CPU3__-CPU1_DS_E_1_2
Since 2001, CJ1M-series PLCs are in
control of a wide variety of
applications worldwide.
The accumulated experience and
advancements in technology now
result in CJ2M; fully compatible, yet
fully new.
• Increased performance, and increased memory capacity
• Up to 40 I/O units on any CPU
• USB for plug-and-play access to the PLC
• All models available with or without Ethernet port
• Choice of serial port plug-in modules
• User-friendly programming, faster debugging
CJ2M-CPU3@
CJ2M-CPU1@
Features
Five variations in program capacity from 5K steps to 60K steps; scale the CPU to your application needs.
Faster processors; LD instruction execution time is reduced to 40 ns, floating point trigonometrics in less than 1 μs.
Faster Function Block calls and execution, faster interrupt handling, less overhead time.
Added execution memory for Function Blocks allows structured, object-oriented programming even in entry-level CPUs.
General-purpose Ethernet port supports EtherNet/IP tag-based data links, connection to Support Software, communications between PLCs,
FTP data transfers, and more (CJ2M-CPU3@).
Standard USB port on all models allows Support Software to connect directly through standard USB cable.
A Serial Option Module can be mounted to add RS-232C or RS-422A/485 communications ports (CJ2M-CPU3@).
Compatible with all existing CJ1 power supply-, I/O-, control- and communication units.
1

1 Page





CJ2M-CPU32 pdf, ピン配列
Accessories
CJ2M-CPU3@/-CPU1@
www.DataSheet4U.com
The following accessories come with CPU Unit:
Item
Specification
Battery
CJ1W-BAT01
End Cover
CJ1W-TER01 (necessary to be mounted at the right end of CPU Rack)
End Plate
PFP-M (2 pcs)
Serial Port (RS-232C) Connector
(see note)
Connector set for serial port connection (D-SUB 9-pin male connector)
Note: Connector is not provided with CJ2M-CPU3@.
General Specifications
Item
Enclosure
Grounding
CPU Rack Dimensions
Weight
Current Consumption
Ambient Operating Temperature
Ambient Operating Humidity
Atmosphere
Ambient Storage Temperature
Altitude
Pollution Degree
Use Environment
Noise Immunity
Overvoltage Category
EMC Immunity Level
Vibration Resistance
Shock Resistance
Battery
Life
Model
Applicable Standards
Note: Without a Serial Option Board.
CJ2M-
CPU1@
CPU3@
Mounted in a panel
Less than 100
90 mm × 75 mm × 31 mm
90 mm × 75 mm × 62 mm
130 g or less
190 g or less (see note)
5 VDC, 0.5 A
5 VDC, 0.7 A
0 to 55°C
10% to 90%
Must be free from corrosive gases.
20 to 70°C (excluding battery)
2,000 m or less
2 or less: Conforms to JIS B3502 and IEC 61131-2.
2 kV on power supply line (Conforms to IEC 61000-4-4.)
Category II: Conforms to JIS B3502 and IEC 61131-2.
Zone B
Conforms to IEC60068-2-6
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each =
100 min total)
Conforms to IEC60068-2-27
147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units)
5 years at 25°C
CJ1W-BAT01
Conforms to cULus and EC Directives.
3


3Pages


CJ2M-CPU32 電子部品, 半導体
CJ2M-CPU3@/-CPU1@
www.DataSheet4U.com
Item
Logical Ports for
Communications
Logical Ports
Extended Logical
Ports
CIP
Communications
Specification
Class 3 (Connection
Type)
UCMM (Non-
connection Type)
Peripheral (USB) Port
Baud Rate
Transmission Distance
Serial Port
Communications Method
Synchronization Method
Baud Rate
Transmission Distance
EtherNet/IP Port
Media Access Method
Modulation
Transmission Paths
Baud Rate
Transmission Media
Transmission Distance
CJ2M-
CPU11/31
CPU12/32
CPU13/33
CPU14/34
8 ports (Used for SEND, RECV, CMND, PMCR, TXDU, and RXDU instructions.)
64 ports (Used for SEND2, RECV2, CMND2, and PMCR2 instructions.)
CPU15/35
Number of connections: 64
Maximum number of clients that can communicate at the same time: 32
Maximum number of servers that can communicate at the same time: 40
USB 2.0-compliant B-type connector
12 Mbps max.
5 m max.
CJ2M-CPU1@ interface: Conforms to EIA RS-232C.
CJ2M-CPU3@: No serial ports with default system
One of the following Serial Option Boards can be mounted.
CP1W-CIF01 RS-232C Option Board
CP1W-CIF11 RS-422A/485 Option Board (not isolated, max. transmission distance: 50 m)
CP1W-CIF12 RS-422A/485 Option Board (isolated, max. transmission distance: 500 m)
Half-duplex
Start-stop
0.3, 0.6, 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 (kbps)
15 m max.
CSMA/CD
Baseband
Star
100 Mbps (100Base-TX)
Shielded twisted-pair (STP) cable; Categories: 5, 5e
100 m (between hub and node)
Number of Cascade Connections
No restrictions if switching hub is used.
Commu-
nications
CIP Communications: Tag Data Links
Number of Connections
32
Packet Interval (Refresh period)
1 to 10,000 ms (Unit: 0.5 ms)
Can be set for each connection. (Data will be refreshed at the set interval, regardless of the number
of nodes.)
Permissible Communications Band 3,000 pps *5
Number of Registerable Tag
32
Type of Tags
CIO, DM, EM, HR, WR, and Network symboles
Number of Tags per Connection 8 (Seven tags if PLC status is included in the segment.)
Maximum Link Data Size per Node 640 words
Maximum Data Size per Connection
20 words
(Data is synchronized within each connection.)
Number of Registrable Tag Set
32 (1 connection = 1 segment)
Maximum Tag Set Size
20 words (One word is used when PLC status is included in the segment.)
Maximum Number of Tags
Refreshable in a Single Cycle of
CPU Unit *6
Output/send (CPU Unit to EtherNet/IP): 32
Input/receive (EtherNet/IP to CPU Unit): 32
Data Size Refreshable in a Single Output/send (CPU to EtherNet/IP) : 640 words
Cycle of CPU Unit *6
Input/receive (EtherNet/IP to CPU): 640 words
Change of Tag Data Link Parameter
Settings during Operation
OK *7
Multi-cast Packet Filter *8
OK
CIP Communications: Explicit
Messages
Class 3 (Connection Type)
Number of connections: 128
UCMM (Non-connection Type)
Maximum number of clients that can communicate at the same time : 16
Maximum number of servers that can communicate at the same time: 16
CIP Routing
OK
(CIP routing is enabled for the following remote Units: CJ1W-EIP21, CJ2H-CPU6@-EIP, CJ2M-
CPU3@, and CS1W-EIP21.)
FINS Communications
FINS/UDP
OK
FINS/TCP
16 connections max.
EtherNet/IP Conformance Test
Conforms to A5.
EtherNet/IP Interface
10Base-T/100Base-TX
Auto Negotiation/Fixed Setting
6

6 Page



ページ 合計 : 17 ページ
 
PDF
ダウンロード
[ CJ2M-CPU32 データシート.PDF ]


データシートを活用すると、その部品の主な機能と仕様を詳しく理解できます。 ピン構成、電気的特性、動作パラメータ、性能を確認してください。


共有リンク

Link :


部品番号部品説明メーカ
CJ2M-CPU31

SYSMAC CJ-series CJ2M CPU Units

Omron
Omron
CJ2M-CPU32

SYSMAC CJ-series CJ2M CPU Units

Omron
Omron
CJ2M-CPU33

SYSMAC CJ-series CJ2M CPU Units

Omron
Omron
CJ2M-CPU34

SYSMAC CJ-series CJ2M CPU Units

Omron
Omron


www.DataSheet.jp    |   2020   |  メール    |   最新    |   Sitemap