DataSheet.es    


PDF APR50-B420L Data sheet ( Hoja de datos )

Número de pieza APR50-B420L
Descripción AC Current transducer APR-B420L
Fabricantes LEM 
Logotipo LEM Logotipo



Hay una vista previa y un enlace de descarga de APR50-B420L (archivo pdf) en la parte inferior de esta página.


Total 2 Páginas

No Preview Available ! APR50-B420L Hoja de datos, Descripción, Manual

AC Current transducer APR-B420L
Split core transducer for the electronic measurement distorted AC
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). Switch selectable
ranges and True RMS 4-20mA current output.
IPN = 10 .. 400 A
Preliminary
Electrical data
Primary Nominal Current
IPN (A.t.RMS)
10,25,50
50,75,100
100,150,200
200,300,400
Analogue Output Signal
IOUT (mA)
4-20
4-20
4-20
4-20
Type
APR 50 B420L
APR 100 B420L
APR 200 B420L
APR 400 B420L
R Load resistance
L
< 350
VC Supply voltage (loop powered)
+24 V DC
Vd R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn 5 kV
Limitation of output current
< 25 mA
Accuracy-Dynamic performance data
X
εL
IOE
εIOT
TC G
t
r
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (0 .. ± IPN)
Electrical offset current, TA = 25°C
Thermal drift of IOE
Thermal drift of the gain (% of reading)
Response time @ 90% of I
P
Frequency bandwidth (-3 dB)
< ±1 % of IPN
< ±0.5 % of IPN
4 mA
±1 µA/K
±0.1 %/K
< 1000
ms
10 .. 6000 Hz
General data
T Ambient operating temperature
A
T Ambient storage temperature
S
m Mass
-20 .. +60
-20 .. +85
90
°C
°C
g
Protection type
IP20
Reliable isolation according to EN50178, EN61010 300
V AC
Creepage distance
> 5.5
mm
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
Features
VFD and SCR waveforms current
measurement
True RMS output
Split core type
Loop powered 4-20mA current output
DIN mounting & Panel mounting
Eliminates insertion loss
Switch selectable ranges
Advantages
Large aperture for cable up to Ø18mm
High isolation between primary and
secondary circuits
Easy to mount
Applications
VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
SCR Controlled Loads:
Acurate measurement of phase angle
fired or burst fired (time proportioned)
SCRs. Current measurement gives
faster response than temperature
measurement.
Switching Power Supplies and
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Notes : Installation and maintenance should be done with power supply disconnected.
LEM Components
030708/0
www.lem.com

1 page





PáginasTotal 2 Páginas
PDF Descargar[ Datasheet APR50-B420L.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
APR50-B420LAC Current transducer APR-B420LLEM
LEM

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar