FEATURES
Interfaces, amplifies, & filters a process-current input.
Process-current input signals are measured by reading the
voltage across an external precision 100Ω resistor (supplied
with module).
Module provides simultaneous precision voltage and
current outputs.
Module circuitry can withstand 220v rms at the input screw-
terminals.
All 3B32 series modules are mix-and-match and Hot
Swappable.
APPLICATIONS
Industrial signal conditioning
Industrial signal isolation
Industrial signal filtering
PRODUCT OVERVIEW
The 3B Series of Signal Conditioning I/o Subsystems provide a
low-cost, versatile method of transferring analog transducer
signals to a data acquisition, monitoring or control system
without the inherent noise, non-linearity, drift and extraneous
voltages. The modules are designed to directly accept analog
signals from Thermocouples, RTD’s, AC and DC Strain Gages,
Torque Transducers, Frequency Transducers, LVDTs, millivolt
or process current signals. The modules amplify, isolate,
linearize and convert the transducer output signals to
standardized analog inputs for high-level analog I/O
subsystems. The 3B Series Subsystem consists of a 10” relay
rack with universal mounting backplane and a family of plug-in
(up to 16 per rack) input and output signal conditioning
modules.
Eight and four channel backplanes are also available. Each
backplane incorporates screw terminals for sensor inputs and
current outputs and a 26-pin connector for high-level single-
ended voltage outputs to the user’s equipment.
The input modules feature complete signal conditioning
circuitry optimized for specific sensors or analog signals and
provide two simultaneous high-level analog outputs: 0 to +10V
(or +10V) and 4-20 mA (or 0-20 mA).
Rev. 0
Information furnished by Analog Devices is believed to be accurate and reliable.
However, no responsibility is assumed by Analog Devices for its use, nor for any
infringements of patents or other rights of third parties that may result from its use.
Specifications subject to change without notice. No license is granted by implication
or otherwise under any patent or patent rights of Analog Devices. Trademarks and
registered trademarks are the property of their respective companies.
Isolated, Process Current Input
3B32
FUNCTIONAL BLOCK DIAGRAM
Figure 1. 3B32 Functional Block Diagram
Output modules accept 0 to +10V (or +10V) single-ended
signals and provide an isolated 4-20 mA (or 0-20 mA) process
signal. All modules feature a universal pin-out and may be
readily hot-swapped under full power and interchanged without
disrupting field wiring.
The Analog Devices 3B Series Signal Conditioning Subsystem is
designed to easily handle signal conditioning problems in
measurement and control applications. Some typical uses are in
microcomputer-based data acquisition systems, programmable
controllers, analog recorders, dedicated control systems, and any
other applications where monitoring of temperature, pressure,
flow and analog signals are required. Since each input module
features two simultaneous outputs, the voltage output can be
used to provide an input to a microprocessor-based data
acquisition or control system while the current output can be
used for analog transmission, operator interface, or an analog
backup system.
Each input module is a single-channel signal conditioner which
plugs into a socket on the backplane and accepts its signal from
the input screw terminals. All input modules provide input
protection, amplification and filtering of the input signal,
accuracy of +0.1%, low drift of +1 uV/oC (low-level input
modules), and feature two high-level analog outputs that are
compatible with most process instrumentation. The isolated
input modules also provide +1500 V peak isolation.
The choice of a specific 3B module depends upon the type of
input signal. Input modules are available to accept millivolt, volt,
process current, thermocouple, RTD, AC and DC strain gage,
frequency and LVDT inputs. The voltage output of each module
is available from the system I/O connector while the current
output is available on the output screw terminals.
One Technology Way, P.O. Box 9106, Norwood, MA 02062-9106, U.S.A.
Tel: 781.329.4700
www.analog.com
Fax: 781.326.8703 © 2004 Analog Devices, Inc. All rights reserved.
1 Page 3B32
3B32 Models Available
Model
3B32-00
Input Range
Externally Programmable2
3B32-01
4 mA to 20 mA
3B32-02
0 mA to20 mA
3B32-Custom
*
1 Output current range may be user programmed to 4 mA to 20 mA using jumper supplied.
2 Requires AC1310 ranging card.
* Custom Input/Output ranges are available. Refer to configuration guide.
Output Ranges1
-10 V to ±10 V & 0 mA to 20 mA
0 V to ±10 V & 4 mA to 20 mA
0 V to ±10 V & 4 mA to 20 mA
*
3B32 Specifications
(typical @ +25°C and ±15 V dc, and +24 V dc Power)
Description
Model 3B32
Input Ranges
Standard Ranges
0 mA to 20 mA; 4 mA to 20 mA
Custom Ranges
0 mA to 20 mA (refer to ordering section)
Output Ranges
Voltage (RL > 2 KΩ)
Current (RL = 0 to 850Ω)1
Maximum Current Output Span
0 V to +10 V; -10 V to +10 V
4 mA to 20 mA or 0 mA to 20 mA
0 mA to 31 mA
Accuracy2
Initial @ +25°C
±0.1% Span
Nonlinearity
±0.01% Span
Stability vs. Temperature
Voltage Output
Zero
±25 ppm of Span/°C
Span
Current Output3
±25 ppm of Reading/°C
Zero
±25 ppm of Span/°C
Span
Zero and Span Adjustment Range4
±25 ppm of Reading/°C
±5% of Span
Value
Accuracy
Stability vs. Temperature
Input Bias Current
Input Resistor
100 Ω
±0.1%
±0.002%/°C
+3 nA
Rev. 0 | Page 3 of 8
3Pages OUTLINE DIMENSIONS
3B32
Figure 5. Outline Dimensions
Rev. 0 | Page 6 of 8
6 Page | |||
ページ | 合計 : 8 ページ | ||
|
PDF ダウンロード | [ 3B32-01 データシート.PDF ] |
データシートを活用すると、その部品の主な機能と仕様を詳しく理解できます。 ピン構成、電気的特性、動作パラメータ、性能を確認してください。 |
部品番号 | 部品説明 | メーカ |
3B32-00 | Isolated/ Process Current Input | Analog Devices |
3B32-01 | Isolated/ Process Current Input | Analog Devices |
3B32-02 | Isolated/ Process Current Input | Analog Devices |